Setting the Input Voltage Range for the Eaton 9SX2000 UPS

What is Affected

When a UPS overload or internal failure occurs, the attached equipment is transferred to utility power (bypass mode). However, the utility power continues to be passively filtered, provided that it meets the bypass high and low limits set for the unit.

The voltage specification for the Panther System is 90–253V. In order to meet this specification in different regions where the Panther System is used, the bypass high and low limit voltages on the Panther System UPS must be configured according to the settings in the following table.

UPS
Version
Input Voltage
Observed
(Step 2b)

Output Voltage
Observed
(Step 3d)

Bypass Low Limit % Setting
(Step 4d)
Bypass Low Limit Voltage Cutoff Bypass High Limit % Setting
(Step 4f)
Bypass High Limit Voltage Cutoff

North America
110V

90–105 100 -10% 90 15% 115
106–115 110 -15% 93.5 15% 126.5
116–123 120 -15% 102 15% 138
124–135 127 -15% 107.95 15% 146.05

International
220V

180–205 200 -15% 170 15% 230
206–215 208 -15% 176.8 15% 239.2
216–225 220 -15% 187 15% 253
226–235 230 -15% 207 10% 253
236–250 240 -15% 216 5% 252

Parts and Materials Required

  • Eaton 9SX2000 UPS for 120V (North America)

    OR

  • Eaton 9SX2000G UPS for 220V (International)
  • OR

  • EATON Powerware 9SX UPS, 110V

  • OR

  • EATON Powerware 9SX UPS, 220V

Procedure

Note—
ALL Fusion Installs require the Output Voltage on the UPS to be set at 220V.
  1. Ensure the UPS is installed and powered on, with the correct power cord for the country of installation.
    Note—Although the cords for some countries may physically fit into the sockets of other countries, the wrong cord will generate wiring fault alarms. To avoid this issue, ensure that the correct cord is used.
    Note—To Access the Main Menu on the UPS, press until the EATON logo displays on the screen.
  2. Input Voltage Observed by the UPS (i.e., voltage supplied from the wall socket):
    1. Highlight Measurements on the Main Menu using the up and down arrow buttons, and press the button.
    2. ClosedPress the button to highlight Input/Output on the screen and press the button.

    3. ClosedRefer to the Input Voltage Observed column in the table above to determine the appropriate settings to be used in the following steps. The Output Voltage, Bypass Low Limit %, and Bypass High Limit % settings will be based on the Input Voltage observed in the previous step.

  3. Output Voltage Setting (based on the Input Voltage Observed from Step 2b):
    1. ClosedFrom the Main Menu, press the button to highlight Settings, then press the button.

    2. ClosedPress the button to select In/Out settings, then press the button.

    3. ClosedOutput Voltage should be highlighted, press the button.

    4. ClosedPress the or button until the desired Output Voltage appears (based on the Input Voltage Observed from Step 2b), then press the button.

  4. Bypass Low and High Limit Settings (based on the Output Voltage selected in Step 3d). 
    1. ClosedFrom the Main Menu, press the button to highlight Settings, then press the button.

    2. ClosedPress the button to select In/Out settings, then press the button.

    3. ClosedPress the button until Bypass settings is highlighted, then press the button.

      Note—ClosedIf the desired low limit is displayed, skip to Step 4e. If not, continue to Step 4d.

    4. ClosedPress the button until the desired Low Limit % Setting appears (based on the Input Output Voltage set in Step 3d), then press the button.

    5. Press the button to highlight Volt High appears, then press the button.
      Note—If the desired high limit is displayed, press the button and skip to Step 4g. If not, continue with Step 4f.
    6. Press the button until the desired High Limit % Setting appears (based on the Input Output Voltage set in Step 3d), then press the button.
    7. Press ESC three times to return to the Main Menu.