Eaton UPS Alarm Settings for MS Windows 10

Parts and Materials Required

  • None

Time Required

  • 10 Minutes

Procedure

Note—
ALL Fusion Installs require the Output Voltage on the UPS to be set at 220V.
  1. Navigate to Tasks in the Panther GUI.
  2. ClosedClick on Perform Maintenance.

  3. ClosedSelect Service.

  4. ClosedSelect UPS Configuration.

  5. ClosedThe UPS Configuration window opens, displaying the current alarm thresholds.

  6. ClosedEdit the UPS alarm threshold according to the following table:

    1. Leave the Warning Threshold at 70%.
    2. ClosedTap or click on 40% (Safe Shutdown) and use the on screen keypad to change that value to 55%. Click OK.

    3. Use the same technique to change the 15% Critical Shutdown) value to 25%.
  7. ClosedTake a screenshot of the configuration screen showing the new alarm configuration, saving it with a filename that includes the system serial number and date (example: 01234_UPS_Alarms_12Jul2019).

  8. Click OK and exit the UPS Configuration screen.

Verification

None